Alkali & Sludge Conditioner for Low Pressure Steam & Industrial Hot Water Systems

Alkali & Sludge Conditioner for Low Pressure Steam & Industrial Hot Water Systems

Accepta 2815 is a high performance liquid formulation containing an alkali and effective sludge conditioner. This highly effective coagulation programme is primarily formulated for conditioning boiler feed water with medium to high hardness (in excess of 60 ppm total hardness).

Applications for Accepta 2815 are mostly for low pressure steam plants or industrial hot water systems that are not atmospherically balanced or pressurised with air.

Accepta 2815 may be used as a single treatment or in combination with other suitable products where necessary.

When use situations necessitate Accepta 2815 is in compliance with US FDA regulations relating to Boiler Water Additives (21 CFR 173.310).

Product Benefits

Excellent single product coagulation programme for conditioning boiler feed water with medium to high hardness.

Ideal for low pressure steam plants or industrial hot water systems that are not atmospherically balanced or pressurised with air.

Complies with US FDA regulations, Boiler Water Additives (21 CFR 173.310).

Product Properties

Form: Liquid
Colour: Dark brown
Odour: Slightly fishy
Relative density: 1.25 - 1.29 g/cm3
Solubility in water: Complete
pH (neat, 20°C): >12
Freezing point: < -22 oC
Alkalinity Furnish: 29 to 31% (as CaCO3)

*Full details of the product properties are available in the Safety Data Sheet. See below.

Application & Dosage Information


Product dosage is based on the feed water total harness and total alkalinity. In a coagulation programme, alkalinity is usually used to control treatment dosage.  The "P" alkalinity is normally set between the extreme limits of 150 ppm to 500 ppm.


Accepta 2815 should be fed continuously to the feed water for maximum scale and corrosion control. Under certain circumstances, it may be "slug" fed for alkalinity elevation using a suitable feeder.

Accepta 2815 is preferably fed neat directly using a chemical feed pump.

Step 1


1Feedwater total hardness (THF)

Feedwater total alkalinity (MF)

Feedwater flow (kg.day-1)

Boiler cycles of concentration (n)

Step 2

Determine dosage factor for total hardness: ppm dosage for hardness = 3.35


Step 3

Determine total dosage for alkalinity and total suspended solids control:

ppm dosage for alkalinity and total suspended solids control = (2500 / n) - (3.33*MF)

Step 4

Determine total dosage:

Total dosage = Dosage Step 1 + dosage Step 2

Testing & Control

Product control is based on alkalinity measurement of boiler water.The "P" alkalinity in the boiler water should be maintained between 150 and 500 ppm.

It is always advisable to carry out a 'Control Of Substances Hazardous to Health' (COSHH) assessment before use.

Safety, Storage & Handling

For full details concerning safety precautions, storage and handling procedures for Accepta 2815 please refer to the latest Safety Data Sheet. To download the latest safety data for this product use the following link:

Safety Data for Accepta 2815

Popular Boiler Water Treatment & Related Products

World Class Expertise

Accepta work with industry worldwide delivering practical, cost effective solutions to resolve complex problems. If you require technical assistance, or information about our water treatment chemicals and other speciality products, please contact our dedicated technical support team on:

+44 (0) 845 519 89 90 or complete our Technical Support form.

Expert Training

Develop your skills with our internationally recognised water and wastewater treatment training courses. Delivered by world leading industry experts and designed for engineers, facilities managers and environmental professionals... water treatment training.

Keep upto date with our extensive library of good practice guides, latest research, regulatory updates, news and more... knowledge base.

Custom Chemical Manufacturing

Accepta offer custom chemical manufacturing, specialist toll blending and white label production services for our own water treatment chemicals and client specific formulations to UK and international customers.

To discover how you could benefit from our environmentally sensitive, quality driven chemical manufacturing capabilities please call us on +44 (0) 161 877 2334 or contact us.

International Distributor Opportunities

Accepta's innovative, quality driven customer focused business model creates exciting global supply chain and distributor opportunities for established and ambitious businesses currently active within the water treatment, wastewater treatment and environmental services sectors around the world.

If you are interested in becoming an exclusive international distributor of Accepta water treatment technologies please click here to learn more.

bsi-ukas-14001-2004bsi-ukas-9001-2008british-association-for-chemical-specialitiesinvestors-in-people-iip  greater-manchester-chamber-of-commerce-member